menu_logo

menu_view_template done edit menu_subscribe menu_add menu_publish iOS Create Account Login
menu_clear
  • menu_insert_row
  • menu_delete_row
  • menu_insert
  • menu_share_template
  • menu_share_results
  • menu_duplicate
  • menu_view_source
  • menu_view_calc_log
  • menu_settings
  • menu_tags
  • help
  • menu_profile
  • menu_log_out
menu_preview_only
details_tap
details_type
details_title

Gas Pipe Calculator

D =
Q =
P1 =
P2 =
Y =
Cr =
L =

Help

D = inside diameter of pipe
Q = input rate appliance(s), cubic feet per hour at 60°F and 30 in. mercury column
P 1 = upstream pressure, psia (P1 + 14.7)
P 2 = downstream pressure, psia (P2 + 14.7)
DP = P1 - P2
L = equivalent length of pipe, ft
H = pressure drop, in. w.c. (27.7 in. H2O = 1 psi)
Formula Factors
Gas. Natural Gas. Undiluted Propane
Cr. 0.6094. 1.2462
Y. 0.9992. 0.991
From International Fuel Gas Code
IFGC 402.4 Equation 4-2
Contributed by Mark Sweeney

Examples

Here are the calculated results:
D: 6.065
Q: 250,000
P1: 29.7
P2: 28.6941351101
Y: 0.9992
Cr: 0.6094
L: 100
Example 2:
D: 0.622
Q: 645.231480698
P1: 18.7
P2: 17
Y: 0.9992
Cr: 0.6094
L: 100

Keywords

D
Q
P1
P2
Y
Cr
L
-------------
Pressure drop
length
pipe
pressure
input rate appliance